Home > Product > Power Testing Equipment > Intelligent Discharge Tester

PM6C Electric control unit

Call now for consultation+86 13360548789
Overview/Features Technical Structure Wiring

PM6C switch control unit

1 Function description

Ø 24 relay outputs, can do 24 fault dry contacts or 12 electrical opening and closing controls

Ø Provides two communication methods: RS485 and CAN

2 Hardware description

PM6C technical parameters

Ø Supply voltage: 80VDC-320VDC

Ø Relay output: 24 channels, capacity DC220V/0. 4A

Ø Communication port: isolated RS485, CAN

PM6C interface description

Serial number

Interface definition

Pin screen printing

Pin Definition

J1

power supply

PWR-

Negative electrode of working   power supply

PWR +

Positive pole of working power   supply

PE

Earth

J2

485 communication port

485A

RS485A

485B

RS485B

J3

CAN communication port

CANH

CANH

CANL

CANL

J4

RJ45 communication port

4. CANH

CANH

5. CANL

CANL

7.485 A

RS485A

8.485 B

RS485B

J5

RJ45 communication port

4. CANH

CANH

5. CANL

CANL

7.485 A

RS485A

8.485 B

RS485B

J6 to J11

Relay Output 1

N0 _ 1

First path (normally open) node 1

COM _ 1

First path (normally open) node 2

Relay Output 2

N0 _ 2

Second (normally open) node 1

COM _ 2

Second path (normally open) node 2

Relay Output 24

N0 _ 24

24th (normally open) node 1

COM _ 24

24th (normally open) node 2

SW

DIP switch

1 Addr

Address dialing code

2 Addr

Address dialing code

3 Addr

Address dialing code

4 Addr

Address dialing code

5 Rsv

Alternate dial code

6 Mode

Mode dial code

LED1

Red LED

Alarm

Warning lamp

LED2

Green LED

work

Work light

There is DC high voltage on% J1, so pay attention to operation safety during maintenance operations.

IMPORTANT WIRING INSTRUCTIONS FOR PM6C

Output control mode: PM6C can be used as a fault dry contact output or as an electric switch control output, but the same PM6C can only use the same mode, and the two modes cannot be mixed.

Electric switch control wiring: Each electric switch requires 2 control points: closing/opening. When the PM6C is set to the electric control mode, the odd serial number is fixed as the closing control point, and the even serial number is fixed as the opening control point. That is, the relay output 1/3/5... is closing control, and the relay output 2/4/6... is opening control; 1/2 of the relay output forms an electrically operated switch control, and so on.

PM6C Construction and Installation:

The installation size and fixed opening size are consistent with PM6A.

Installation dimensions: 224.3 mm × 110.3 mm, height 35.6 mm

Fixed opening size: 213.5 mm × 82 mm, fixed with M3 screws.

PM6C unit setup instructions:

DIP setting sampling binary mode; Dial "ON" is 0, dial "OFF" is 1

Serial number

Dial code 1

Dial code 2

Dial code 3

Dial code 4

Address

1

ON

ON

ON

ON

1#

2

ON

ON

ON

OFF

2#

16

OFF

OFF

OFF

OFF

16#

Dial code 6. InsSel: ON is dry contact mode; OFF is the electric operation mode.

1.3. 2.7 PM6US Integrated Measurement Unit

1 Function description

Ø Detect two single-phase or three-phase AC voltages and contactor status, and control two AC contactors.

Ø Detect 3 DC voltages and bus insulation.

Ø All-way ambient temperature detection.

Ø Detect 29 analog inputs, including detecting 22 switches, battery switches, fuses, two AC contactors, lightning protectors, battery current and bus control current.

Ø Control 6 dry contact outputs and control silicon chains.

2 Technical parameters

Ø Power supply voltage: 80VDC-300VDC;

Ø Communication port: isolate RS485 communication;

Ø Detection range and error:

Measured signal

Error

Measurement range

remark

Three-phase AC voltage

≤ 2% at more than 200V

0-480V


Joint mother/battery/control   mother

≤ 0. 5% at more than 80V

0-300V


 

Interface Description

 

Interface definition:

Serial number

Interface definition

Pin screen printing

Pin Definition

J1

DC 24V output

24V +

24V positive pole

24V-

24V negative

J2

AC 1-way voltage sampling

AC1 _ U

AC 1 U phase voltage (single phase   U)

AC1 _ V

AC 1 V phase voltage (single phase   V)

AC1 _ W

AC 1-way W-phase voltage

J3

AC 2-way voltage sampling

AC2 _ U

AC 2-way U-phase voltage   (single-phase U)

AC2 _ V

AC 2-way V-phase voltage (single   phase V)

AC2 _ W

AC 2-way W-phase voltage

J4

Silicon chain control

+12V

Silicon chain controlled power   supply

GLK1

Silicon chain control port 1

GLK2

Silicon chain control port 2

GLK3

Silicon chain control port 3

J5

Dry contact output

No _ 1

First (normally open) node 1

COM _ 1

First path (normally open) node 2

NO _ 2

Second (normally open) node 1

COM _ 2

Second path (normally open) node 2

NO3

Third (normally open) node 1

COM _ 3

Third (normally open) node 2

NO4

Fourth path (normally open) node 1

COM _ 4

Fourth path (normally open) node 2

NC _ 5

Fifth (normally open) node 1

COM _ 5

Fifth path (normally open) node 2

J6

Dry contact output

NC

Normally closed (power-down   closed) node 1

COM

Normally closed (power-down   closed) node 2

J7

AC contactor control

CTLA

1-way AC contactor control

CTLB

2-way AC contactor control

J8

Dry contact detection

S01

Switching value detection input 1

S02

Switch value detection input 2

S03

Switching value detection input 3

S04

Switch value detection input 4

S05

Switching value detection input 5

S06

Switching value detection input 6

S07

Switch Value Detection Input 7

S08

Switching value detection input 8

J9

Dry contact detection

S09

Switching value detection input 9

S10

Switching value detection input 10

S11

Switching value detection input 11

S12

Switching value detection input 12

S13

Switching value detection input 13

S14

Switching value detection input 14

S15

Switching value detection input 15

S16

Switching value detection input 16

+12V

Switch detection input common   point

J10

Dry contact detection

S17

Switching value detection input 17

S18

Switching value detection input 18

S19

Switching value detection input 19

S20

Switching value detection input 20

S21

Switching value detection input 21

S22

Switching value detection input 22

BATK

Battery switch detection input

FUSE

Fuse detection input

J11

Dry contact detection

AST

1-way AC contactor status   detection

BST

2-way AC contactor status   detection

FLQ

Lightning Protector Detection

+12V

Switch detection input common   point

J12

Contact detection

BATI

Cell Current

KMI

Bus control current

+12V

Positive 12V

GND

Ground

-12V

Minus 12V

J13

Communications 485

485A

RS485A

485B

RS485B

J14

power supply

PWR-

Negative electrode of working   power supply

PWR +

Positive pole of working power   supply

PE

Earth

J15

DC bus sampling

BAT-

Battery voltage negative

BAT

Positive battery voltage

HM +

Positive bus voltage

KM +

Positive bus voltage

MX-

Busbar voltage negative

J16

Temperature detection

GND

Temperature sampling place

TMP

Temperature sampling

LED1

Red LED

Alarm

Warning lamp

LED2

Green LED

work

Work light



Structural and installation dimensions

The installation size is 215mm × 108mm, the height is 53mm, the fixed opening size is 205mm × 82mm, and it is fixed by M3 screws.

As shown in the image below

Sampling Wiring Instructions

J1 DC 24V output: main monitoring power supply use.

J2, J3 AC voltage sampling: If single-phase AC is collected, connect to AC1 _ U, AC1 _ V and AC2 _ U, AC2 _ V.


Technical

Structure

Wiring

Online message

Please fill in the following form, we will receive your information after the first time to contact you, if you have questions, please call.

  • Product*

  • Company

  • Name*

  • Sex*

    Sir Miss
  • Phone*

  • Email

  • Message*

Contact Us

Sales service phone number:

+86 13360548789

After-sales service phone number:

0755-27521182 or 27521325